Continuous electricity cable monitoring now a reality: Greater reliability at reduced cost

In collaboration with KEMA, two postgraduate students from Eindhoven University of Technology have developed a device that continuously monitors cables to localize weak points in distribution networks. Data on weak point development and location enables an electricity company to pre-empt problems by timely intervention. This in turn enhances network reliability and reduces costs. With their invention, Jeroen Veen and Peter van der Wielen received in April their doctorate degree at the Eindhoven University of Technology.

Continuous monitoring

Most power network faults are down to defective distribution cables. Electricity companies therefore try to identify weak spots in cables and replace them before short circuits occur. At present, this is done by carrying out periodic checks on critical cables during maintenance shutdowns. As well as being time-consuming and expensive, this process is far from entirely reliable. In the future, however, electricity companies will be able to cheaply and continuously monitor the quality of vital cables while they remain in use, thanks to research undertaken by Jeroen Veen and Peter van der Wielen. The postgraduate duo has developed a working prototype that has now been adopted by a manufacturer.

Short-circuit

As a power cable ages, its insulation is liable to degrade. If the problem isn’t detected in time, this can result in a short circuit fault. At the points where the insulation has deteriorated most, high-frequency electrical discharges occur. These discharges generate current impulses, which travel along the cable and can be detected at the terminals. The new measuring system consists of two specially developed sensors, one at each end of the cable, which register the impulses. Data from the sensors is transmitted via a telephone line to a central server. The server analyses the data to determine whereabouts along the cable the problems are.

Arrival time

Problems are localized by working out the difference in time taken for an impulse from a fault to reach each of the sensors. The Eindhoven-based researchers have come up with a patented method for synchronization of the measurement signals. This means that the lag in impulse arrival times can be accurately determined and the fault localized. Not only is the new technique smart and cheap, it is also unique, because it is the only option so far developed for monitoring cables while they are in use. Testing of the prototype has yielded highly promising results. A deliberately induced fault in a three-hundred-meter cable was localized to within half a meter. The expectation is that the commercial system will be suitable for monitoring cables up to four kilometers long.

Media Contact

Xavier Theunissen alfa

All latest news from the category: Power and Electrical Engineering

This topic covers issues related to energy generation, conversion, transportation and consumption and how the industry is addressing the challenge of energy efficiency in general.

innovations-report provides in-depth and informative reports and articles on subjects ranging from wind energy, fuel cell technology, solar energy, geothermal energy, petroleum, gas, nuclear engineering, alternative energy and energy efficiency to fusion, hydrogen and superconductor technologies.

Back to home

Comments (0)

Write a comment

Newest articles

Recovering phosphorus from sewage sludge ash

Chemical and heat treatment of sewage sludge can recover phosphorus in a process that could help address the problem of diminishing supplies of phosphorus ores. Valuable supplies of phosphorus could…

Efficient, sustainable and cost-effective hybrid energy storage system for modern power grids

EU project HyFlow: Over three years of research, the consortium of the EU project HyFlow has successfully developed a highly efficient, sustainable, and cost-effective hybrid energy storage system (HESS) that…

After 25 years, researchers uncover genetic cause of rare neurological disease

Some families call it a trial of faith. Others just call it a curse. The progressive neurological disease known as spinocerebellar ataxia 4 (SCA4) is a rare condition, but its…

Partners & Sponsors